Grilles & diffusers
Check air velocity at ventilation outlets and compare readings across a grille. Use consistent probe positioning when checking air distribution or balancing a system.
Low air velocity measurement
See the airflow you cannot feel. Measure air velocity and temperature together with a slim telescopic probe built for grilles, diffusers and ventilation checks.
Dual LCD / MAX–MIN recall / RS-232 output
Telescopic probeIncluded carrying case
Practical measurement
From a supply grille to a low-velocity work area, use a separate probe to reach the measurement point while keeping the display in view.
Check air velocity at ventilation outlets and compare readings across a grille. Use consistent probe positioning when checking air distribution or balancing a system.
Evaluate local air movement at low velocities. The 0.2 m/s lower measurement limit and remote probe support spot checks at selected measurement points.
Compare air velocity before and after maintenance, or inspect circulation around a refrigerated display. Read air temperature alongside velocity on the dual LCD.
Use within the specified air velocity, temperature and humidity limits. Spot measurements do not by themselves certify cleanroom performance.
Using the AVM-714
Prepare the sensor, align the probe and capture your readings. Keep fingers and tools away from the delicate sensing element.
Watch the product demonstration ↗Product details
Five selectable air velocity units, temperature in °C or °F, and practical functions for field inspection.
| Measurement | Range | Resolution |
|---|---|---|
|
Air velocity
|
0.2–20.0 m/s | 0.1 m/s |
|
Air velocity
|
0.7–72.0 km/h | 0.1 km/h |
|
Air velocity
|
40–3,940 ft/min | 1 ft/min |
|
Air velocity
|
0.5–44.7 mph | 0.1 mph |
|
Air velocity
|
0.4–38.8 knots | 0.1 knots |
|
Temperature
|
0–50 °C / 32–122 °F | 0.1 °C / 0.1 °F |
Air velocity accuracy:±(5% of reading + 1 digit) or ±(1% of full scale + 1 digit), per the English instruction manual.
Temperature accuracy:±0.8 °C / ±1.5 °F.
Electrical specifications are stated at 23 ±5 °C. Specifications here follow the linked English manual; please confirm the supplied version when ordering.
| Display | Dual LCD; 13 mm digit height |
|---|---|
| Sampling interval | Approximately 0.8 seconds |
| Data output | RS-232 PC serial interface |
| Telescopic probe | 12 mm diameter; 280–940 mm length |
| Operating conditions | 0–50 °C; less than 80% RH |
| Power supply | Six 1.5 V AAA (UM-4) batteries |
| Instrument dimensions | 180 × 72 × 32 mm |
| Weight | 355 g, as specified in the manual |
It measures air velocity and air temperature. Select m/s, km/h, ft/min, mph or knots for air velocity, and °C or °F for temperature.
The documented measurement modes are air velocity and temperature. For volumetric airflow, calculate from representative average air velocity and the effective cross-sectional area, or ask TECPEL about a meter with direct CFM/CMM calculation.
Zero the meter with the sensor cover closed. Open the cover for measurement, then face the mark on the sensor head into the airflow. Avoid touching the sensing element. Refer to the English manual for the complete procedure.
Yes. The AVM-714 provides RS-232 serial output. A compatible interface cable and suitable software are required. Request current accessory options and compatibility information with your quotation.
Talk to TECPEL
Tell us your quantity, destination and application. Ask about availability, shipping and optional PC connection accessories.
sales@tecpel.com.tw